bbk 000000
UDC 628.356.57.001.5
SHVETSOV V. N., MOROZOVA K. M., Smirnova I. I., Semenov Mikhail, Lezhnev M. L., Ryzhakov G. G., Gubaydullin T. M.
The Use of Bioblocks at Wastewater Treatment Facilities
Summary
Results of the laboratory study of an aeration tank operation for the purpose of technological comparison of two new modified bioblocks, BBZ-45P-14 and BBZ-65P-10, having the similar surface structure but different geometric parameters are presented. It is shown that these bioblocks can be used successfully in aeration tanks for immobilization of microorganisms of activated sludge. The tests of loading material samples have been carried out at biomass density in bioblocks of 0,3–0,36 kg/kg, at equivalent concentration of sludge in the system – 2,3 g/l. The bioblock BBZ-65P-10 is used preferably in aeration tanks, BBZ-45P-14 – in aeration tanks with low load on activated sludge, blocks of aftertreatment for additional clarification of water treated biologically and in biofilters for build-up of biological film. The comparison of results of tests on rate of activated sludge adhesion obtained with new types of bioblocks and BBZ-65 tested earlier makes it possible to conclude that the adhesion process goes off more intensively on rougher surfaces of modified models of bioblocks.
Key words
wastewater , biological treatment , biofilter , bioblock , aeration tank , secondary settling tank , adhesion , activated sludge