WATER RECYCLING SYSTEMS

bbk 000000

UDC 628.179.2

Atanov N. A., Kondrat'ev I. I.

Studies on determining thermotechnical characteristics of cooling tower filler

Summary

The results of the experimental studies on determining the process efficiency of redesigned filler in a cooling tower model are presented. The experts of «AIR» CJSC have designed and assembled an experimental cooling tower model for testing the filler and the water catcher. The instrumentation system for measuring temperature at the inlet and outlet, air temperature and humidity, air and cooling water flow rate is described. In the course of aerodynamic tests the coefficients of the filler and water catcher hydraulic resistance were determined; in the course of thermotechnical studies the cooling ability coefficient was determined. The results of the experimental studies of the filler consisting of two blocks with 0.68 m gap between them showed that the filler is of sprinkling-film type and has coo­ling capacity А = 0,44 l/m. The tests carried out in full-scale blocks of the filler and water catcher corresponded to the actual conditions of the cooling tower operation.

Key words

, , , , ,

 

№12|2011

ADVANCED TECHNOLOGIES AND EQUIPMENT

bbk 000000

UDC 624.97:621.175.3

Lezhnev M. L., Ryzhakov G. G., Arefyev Yu. I., Bezzateyeva L. P.

Improving the design of mesh plastic tubular sprinklers

Summary

The results of improving the design of fill media made of mesh plastic tubes alongside with the analysis of the fill media design and process characteristics are presented. It is shown that the dominant factors affecting water cooling in fill media are the surface shape and dimensions that ensure the interaction of water and air flows. The design developed jointly by NII VODGEO OJSC and Techvodpolymer Ltd., that is the new version of Fleron long tubular mesh elements is presented. Depending on the operating conditions of the cooling tower the fill media can be installed either in horizontal, or vertical or inclined position. With specific reference it is shown that at similar water temperature at the input of the cooling tower FleronN fill media ensures 1.6 water concentrations higher compared to BO-65 basic fill media or allows to reduce cooled water temperature by 2.5°C.

Key words

, , , , ,

 