Tag:damages

№9-2|2011

WASTEWATER TREATMENT

bbk 000000

UDC 628.27

Shuvalov M. V., Sopyryaev M. N.

Analysis of City Sewerage Networks Operation

Summary

Results of the analysis of the data base on operation failures of sewerage networks of the city of Samara during the last 9 years of their operation are presented. From the point of view of reliability the gravity sewerage networks are the weakest element of the city wastewater disposal system. According to the statistical data the clogging is the cause of 99% of failures of functioning of the sewerage network. Most of the clogging (over 97%) happens at pipelines of up to 250 mm diameter. In the course of drawing up the schedules of planning-preventive works the operation departments should take into account the seasonality and pay particular attention to the sections of sewerage network with pipes of small diameter. During the reconstruction of gravity sewerage pipelines of less than 250 mm diameter it is recommended to use plastic pipes and pipes of larger diameter.

Key words

, , , ,

 

Журнал ВСТ включен в новый перечень ВАК