Tag:air quality

№3|2019

VENTILATION SYSTEMS

bbk 000000

UDC 697.92

Agafonova V. V.

Indoor air quality assessment in office buildings

Summary

The assessment of indoor air quality in an office building is given. The analysis of the results of reviewing Russian and foreign authors on this topic showed that at CO2 concentration of 600–800 ppm and higher the well-being of people worsens, which leads to impaired productivity and increased fatigue. Prolonged exposure to carbon dioxide in humans can lead to chronic diseases. The results of an experimental study of the change in carbon dioxide concentration in an office of a public building with an area of ​​30 m2 with continuing presence of five people are presented. The CO2 concentration was measured using MT 8057 portable carbon dioxide detector during 24 hours. According to the measurement results a graph of CO2 concentration is plotted against the time. It was concluded that the air quality was not satisfactory during certain periods of the working day (from 10:40 to 13:30 and from 14:45 to 19:00 the CO2 concentration exceeded 1000 ppm) which indicates problems with the ventilation system and excessive sealing of the room (because of plastic windows). The necessity of taking measures to improve the efficiency of inflow exhaust ventilation has been substantiated.

Key words

, , , , , ,

 

Журнал ВСТ включен в новый перечень ВАК

Шлафман В. В. Проектирование под заданную ценность, или достижимая эффективность технических решений – что это?

Banner Kofman 1